Are you planning to upgrade the power network or additionally extend the power line to the kitchen to connect a new electric stove? Minimum knowledge about the cross section of the conductor and the effect of this parameter on power and amperage is useful here.
Agree that incorrect calculation of the cable cross-section leads to overheating and short circuit or to unjustified costs.
It is very important to carry out calculations at the design stage, since the failure of hidden wiring and subsequent replacement involves significant costs. We will help you deal with the intricacies of the calculations in order to avoid problems with the further operation of the power grid.
In order not to burden you with complex calculations, we selected understandable formulas and calculation options, provided information in an accessible form, providing the formulas with explanations. Also, thematic photos and video materials were added to the article, which make it possible to clearly understand the essence of the issue under consideration.
Calculation of the cross section by the power of consumers
The main purpose of the conductors is the delivery of electrical energy to consumers in the required quantity. Since superconductors are not available under normal operating conditions, the resistance of the conductor material has to be taken into account.
The calculation of the required cross-section of conductors and cables depending on the total power of consumers is based on long-term operating experience.
Image Gallery
Photo from
Different types of cable for wiring device
Different thicknesses for conductors for domestic use
Number of cores in various cable brands
Stranded Cable Options
We begin the general calculation process by first performing the calculations using the formula:
P = (P1 + P2 + .. PN) * K * J,
Where:
- P - the power of all consumers connected to the calculated branch in Watts.
- P1, P2, PN - power of the first consumer, the second, n-th, respectively, in Watts.
Having received the result at the end of the calculations according to the above formula, it was time to turn to the table data.
Now you have to choose the required section according to table 1.
Table 1. The cross section of the wire conductors must always be selected in the nearest larger side (+)
Stage # 1 - calculation of reactive and active power
The capacities of consumers are indicated in the documents for the equipment. Typically, equipment certificates indicate active power along with reactive power.
Devices with an active type of load turn all the received electrical energy, taking into account the efficiency, into useful work: mechanical, thermal, or its other form.
Devices with an active load include incandescent lamps, heaters, electric stoves.
For such devices, the calculation of power for current and voltage has the form:
P = U * I,
Where:
- P - power in watts;
- U - voltage in V;
- I - current strength in A.
Devices with a reactive type of load are able to accumulate energy from the source, and then return it. Such an exchange occurs due to the displacement of the sinusoidal current and the sinusoidal voltage.
At zero phase displacement, the power P = U * I always has a positive value. Such a graph of the phases of current and voltage is available for devices with an active type of load (I, i - current, U, u - voltage, π - pi number, equal to 3.14)
Reactive power devices include electric motors, electronic devices of all sizes and purposes, and transformers.
When there is a phase shift between the sinusoidal current and the sinusoidal voltage, the power P = U * I can be negative (I, i is the current, U, u is the voltage, π is the number pi equal to 3.14). Reactive power device returns stored energy back to source
Electric networks are constructed in such a way that they can transmit electric energy in one direction from the source to the load.
Therefore, the returned energy of the consumer with a reactive load is parasitic and is spent on heating conductors and other components.
Reactive power is dependent on the phase angle between the voltage and current sinusoids. The phase angle is expressed in terms of cosφ.
To find the full power, use the formula:
P = Q / cosφ,
Where Q - reactive power in VA.
Typically, the passport data on the device indicates reactive power and cosφ.
Example: in the passport the perforator shows a reactive power of 1200 VAR and cosφ = 0.7. Therefore, the total power consumption will be equal to:
P = 1200 / 0.7 = 1714 W
If cosφ could not be found, for the vast majority of household electrical appliances, cosφ can be taken equal to 0.7.
Stage # 2 - the search for the coefficients of simultaneity and margin
K - dimensionless simultaneity coefficient, shows how many consumers can simultaneously be included in the network. It rarely happens that all devices simultaneously consume electricity.
Simultaneous operation of the TV and music center is unlikely. From established practice, K can be taken equal to 0.8. If you plan to use all consumers at the same time, K should be taken equal to 1.
J - dimensionless safety factor. It characterizes the creation of a power reserve for future consumers.
Progress does not stand still, every year new and surprising new and useful electrical appliances are invented. By 2050, electricity consumption growth is expected to reach 84%. Typically, J is assumed to be from 1.5 to 2.0.
Stage # 3 - performing a geometric calculation
In all electrical calculations, the cross-sectional area of the conductor is taken - the core section. Measured in mm2.
It is often necessary to learn how to correctly calculate the cross-section of a wire according to the diameter of the wire of the conductor.
In this case, there is a simple geometric formula for a monolithic round wire:
S = π * R2 = π * D2/4, or vice versa
D = √ (4 * S / π)
For conductors of rectangular cross section:
S = h * m,
Where:
- S - core area in mm2;
- R - radius of the core in mm;
- D - core diameter in mm;
- h, m - width and height, respectively, in mm;
- π Is the number pi equal to 3.14.
If you purchase a stranded wire, in which one conductor consists of many twisted wires of circular cross section, then the calculation is carried out according to the formula:
S = N * D2/1,27,
Where N - the number of wires in the vein.
Wires having twisted from several wires wires, in general, have better conductivity than monolithic. This is due to the peculiarities of the current flowing through a circular conductor.
Electric current is the movement of the same charges along the conductor. The charges of the same name repel, therefore, the charge distribution density is shifted to the surface of the conductor.
Another advantage of stranded wires is their flexibility and mechanical resistance. Monolithic wires are cheaper and are used mainly for fixed installation.
Stage # 4 — calculate the power section in practice
Task: the total power of consumers in the kitchen is 5000 watts (meaning that the power of all reactive consumers is recounted). All consumers are connected to a single-phase 220 V network and have power from one branch.
Table 2. If you plan to connect additional consumers in the future, the table shows the required capacities of common household appliances (+)
Decision:
The simultaneity coefficient K is assumed to be 0.8. The kitchen is a place of constant innovation, you never mind, a safety factor of J = 2.0. Total estimated capacity will be:
P = 5000 * 0.8 * 2 = 8000 W = 8 kW
Using the value of the design power, we look for the closest value in table 1.
The closest suitable conductor cross section for a single-phase network is a copper conductor with a cross section of 4 mm2. Similar wire size with aluminum core 6 mm2.
For single core wiring, the minimum diameter will be 2.3 mm and 2.8 mm, respectively. In the case of a multicore option, the cross-section of individual cores is added up.
Image Gallery
Photo from
Room with the maximum number of household appliances
Technical equipment of bathrooms and combined bathrooms
Connecting Power Consumers
Block outlet for low power equipment
Hob requires proper connection
Power line for a washing machine
Separate power branches for refrigerators
Powerful energy consumers in bathrooms and bathrooms
Calculation of the current cross section
Calculations of the required cross-section for current and power of cables and wires will present more accurate results. Such calculations make it possible to evaluate the general effect of various factors on conductors, including thermal load, wire grade, type of laying, operating conditions, etc.
The entire calculation is carried out during the following steps:
- power selection of all consumers;
- calculation of currents passing through the conductor;
- selection of a suitable cross section according to the tables.
For this version of the calculation, the current power of consumers with voltage is taken without taking into account correction factors. They will be taken into account when summing the current strength.
Stage # 1 - calculation of the current strength by the formulas
For those who have forgotten the school physics course, we offer the basic formulas in the form of a graphic diagram as a visual cheat sheet:
The "Classic Wheel" demonstrates the interconnection of formulas and the interdependence of the characteristics of electric current (I - current strength, P - power, U - voltage, R - core radius)
Let us write the dependence of the current strength I on the power P and the line voltage U:
I = P / Ul,
Where:
- I - current strength, taken in amperes;
- P - power in watts;
- Ul - line voltage in volts.
Linear voltage in the general case depends on the source of power supply; it is single- and three-phase.
The relationship of the linear and phase voltage:
- Ul = U * cosφ in case of single-phase voltage.
- Ul = U * √3 * cosφ in case of three-phase voltage.
For household electrical consumers, cosφ = 1 is taken, so the linear voltage can be rewritten:
- Ul = 220 V for single phase voltage.
- Ul = 380 V for three-phase voltage.
Next, we summarize all the currents consumed by the formula:
I = (I1 + I2 + ... IN) * K * J,
Where:
- I - total current strength in amperes;
- I1..IN - current strength of each consumer in amperes;
- K - simultaneity coefficient;
- J - safety factor.
The coefficients K and J have the same values that were used in calculating the total power.
There may be a case when in a three-phase network a current of unequal strength flows through different phase conductors.
This happens when single-phase consumers and three-phase consumers are connected to a three-phase cable simultaneously. For example, a three-phase machine and single-phase lighting are powered.
A natural question arises: how is the cross-section of a stranded wire calculated in such cases? The answer is simple - the calculations are made for the most loaded core.
Stage # 2 - choosing a suitable section according to the tables
In the rules for the operation of electrical installations (PES), a number of tables are given for choosing the required cable core section.
Conductor conductivity is temperature dependent. For metal conductors, resistance increases with increasing temperature.
If a certain threshold is exceeded, the process becomes self-sustaining: the higher the resistance, the higher the temperature, the higher the resistance, etc. until the conductor burns out or causes a short circuit.
The following two tables (3 and 4) show the cross-section of the conductors depending on the currents and method of installation.
Table 3. First, you need to choose the method of laying the wires, it depends on how efficiently the cooling takes place (+)
A cable differs from a wire in that all wires equipped with their own insulation are twisted into a bundle and enclosed in a common insulating sheath. More details about the differences and types of cable products are written in this article.
Table 4.An open method is indicated for all values of the cross section of the conductors, however, in practice, cross sections below 3 mm2 are not openly laid for reasons of mechanical strength (+)
When using tables, the following factors are applied to the permissible continuous current:
- 0.68 if 5-6 lived;
- 0.63 if 7-9 lived;
- 0.6 if 10-12 lived.
Decreasing coefficients are applied to the current values from the “open” column.
Zero and grounding conductors are not included in the number of conductors.
According to the PES standards, the choice of the cross section of the zero core for the permissible continuous current is made as at least 50% of the phase core.
The following two tables (5 and 6) show the dependence of the permissible continuous current when laying it in the ground.
Table 5. Permissible continuous current dependences for copper cables when laying in air or ground
The current load when laying open and when deepening into the ground are different. They are taken equal if laying in the ground is carried out using trays.
Table 6. Permissible continuous current dependences for aluminum cables when laying in air or ground
The following table (7) applies to the arrangement of temporary electricity supply lines (carry, if for private use).
Table 7. Permissible continuous current when using portable hose cords, portable hose and mine cables, searchlights, flexible portable wires. Only copper conductors used
When laying cables in the ground, in addition to heat removal properties, it is necessary to take into account the resistivity, which is reflected in the following table (8):
Table 8. Correction factor depending on the type and resistivity of the soil for permissible continuous current, when calculating the cable cross-section (+)
Calculation and selection of copper conductors up to 6 mm2 or aluminum up to 10 mm2 conducted as for continuous current.
In case of large cross sections, it is possible to apply a reduction factor:
0.875 * √Tpv
Where Tpv - the ratio of the duration of the inclusion to the duration of the cycle.
The duration of inclusion is taken from the calculation of no more than 4 minutes. In this case, the cycle should not exceed 10 minutes.
When choosing a cable for wiring electricity in a wooden house, special attention is paid to its fire resistance.
Stage # 3 - calculation of the cross section of the current conductor using an example
Task: calculate the required cross-section of the copper cable for connection:
- 4000 W three-phase woodworking machine;
- 6000 W three-phase welding machine;
- household appliances in the house with a total capacity of 25,000 watts;
The connection will be made by a five-core cable (three phase conductors, one zero and one ground) laid in the ground.
Insulation of cable products is calculated on a specific value of the operating voltage. It should be noted that the manufacturer's operating voltage of his product must be higher than the voltage in the network
Decision.
Step 1. We calculate the linear voltage of a three-phase connection:
Ul = 220 * √3 = 380 V
Step # 2. Household appliances, machine tools and welding machines have reactive power, so the power of machinery and equipment will be:
Pthose = 25000 / 0.7 = 35700 W
Prev = 10000 / 0.7 = 14300 W
Step # 3. Current required to connect household appliances:
Ithose = 35700/220 = 162 A
Step # 4. Current required to connect equipment:
Irev = 14300/380 = 38 A
Step # 5. The required current for connecting household appliances is calculated based on the calculation of one phase. By the condition of the problem, there are three phases. Consequently, the current can be distributed in phases. For simplicity, we assume a uniform distribution:
Ithose = 162/3 = 54 A
Step # 6. Current per phase:
If = 38 + 54 = 92 A
Step # 7. Equipment and household appliances will not work at the same time, except for this we will lay a margin of 1.5. After applying the correction factors:
If = 92 * 1.5 * 0.8 = 110 A
Step # 8 Although the cable contains 5 cores, only three phase cores are taken into account.According to table 8, in a column of a three-core cable in the ground, we find that a current of 115 A corresponds to a cross section of a core of 16 mm2.
Step # 9. According to table 8, we apply the correction factor depending on the characteristics of the earth. For a normal land type, the coefficient is 1.
Step # 10. Optional, calculate the core diameter:
D = √ (4 * 16 / 3.14) = 4.5 mm
If the calculation was made only by power, without taking into account the features of the cable, the cross-section of the core will be 25 mm2. Calculation of the current strength is more complicated, but sometimes it saves significant money, especially when it comes to multi-core power cables.
The relationship between voltage and current can be found in more detail here.
Voltage drop calculation
Any conductor, except superconductors, has a resistance. Therefore, with a sufficient cable or wire length, a voltage drop occurs.
PES standards require that the cross section of the cable core be such that the voltage drop is not more than 5%.
Table 9. Resistivity of common metal conductors (+)
This primarily relates to low-voltage cables of small cross section.
The calculation of the voltage drop is as follows:
R = 2 * (ρ * L) / S,
Upad = I * R,
U% = (Upad / Ulin) * 100,
Where:
- 2 - coefficient due to the fact that the current flows necessarily in two cores;
- R - resistance of the conductor, Ohm;
- ρ - specific resistance of the conductor, Ohm * mm2/ m;
- S - section of the conductor, mm2;
- Upad - voltage drop, V;
- U% - voltage drop with respect to Ulin,%.
Using formulas, you can independently perform the necessary calculations.
Carry calculation example
Task: calculate the voltage drop for a copper wire with a cross section of one core of 1.5 mm2. A wire is needed to connect a single-phase electric welding machine with a total power of 7 kW. Wire length 20 m.
If you want to connect a household welding machine to the mains branch, you should take into account the situation for which the cable is designed. It is possible that the total power of operating devices may be higher. The best option is to connect consumers to individual branches
Decision:
Step 1. We calculate the resistance of the copper wire using table 9:
R = 2 * (0.0175 * 20) / 1.5 = 0.47 Ohm
Step # 2. Current flowing along the conductor:
I = 7000/220 = 31.8 A
Step # 3. Voltage drop on the wire:
Upad = 31.8 * 0.47 = 14.95 V
Step # 4. We calculate the percentage of voltage drop:
U% = (14,95 / 220) * 100 = 6,8%
Conclusion: to connect the welding machine, a conductor with a large cross section is required.
The calculation of the cross section of the conductor according to the formulas:
Recommendations of specialists on the selection of cable and wire products:
The above calculations are valid for copper and aluminum conductors for industrial use. For other types of conductors, the total heat transfer is pre-calculated.
Based on these data, the maximum current capable of flowing through the conductor is calculated without causing excessive heating.
If you have any questions about the methodology for calculating the cable cross-section or have a desire to share personal experience, please leave comments on this article. The feedback box is located below.